TES-1700 |
|
¡ÜCapable of measuring earth voltage.
¡ÜData hold, MAX/MIN function.
¡ÜAuto power off function
¡Ü2mA measuring current permits earth resistance tests
without tripping earth leakage current breakers in the circuit under test.
¡ÜAutomatic warning when resistance of auxiliary earth
spike is in excess of tolerance.
¡ÜDesigned to meet IEC1010-1 safety standard. | |
|
ELECTRICAL SPECIFICATIONS :
* Measuring Range and Accuracy (at 23¡É and 45~75%RH)
Function |
Measuring range |
Accuracy |
Overload Protection |
Earth Voltage |
0 ~ 399.9V (50Hz, 60Hz) |
±(1%rdg+4dgts) |
400Vrms/1 minutes |
Earth Resistance |
0 ~ 39.99§Ù |
±(2%rdg+0.2§Ù) |
250Vrms/10 seconds |
0 ~ 399.9§Ù |
±(2%rdg+3dgts) |
0 ~ 3999§Ù |
* Current Consumption (typical Value with battery voltage of
12V)
Range |
ON |
40§Ù/ 400§Ù/4000§Ù |
58mA |
Earth V |
22mA |
GENERAL SPECIFICATIONS :
- Safety Standard :
IEC1010-1 overvoltage category III , IEC 61557
- Display : 3-3/4 digit liquid crystal display with a maximum
reading of 3999
- Insulation Resistance :
More than 5M§Ù between the circuit and the housing case
when measured with 500VDC
- Withstand Voltage : 3700CV
AC for 1 minute between the circuit and the housing case
- Timer (Auto power off) :
about 3 minutes
- Dimensions : 190(L) ×
140(W) × 77(H)mm
- Weight : Approx. 800(with
battery)
- Power Source : Eight 1.5V
01t AA Size Battery
- Over range Indication :
"OL" will be shown on the LCD panel when
out of
range measurement is
made
- Operating Temperature and Humidity : 0¡É to 40¡É(32¢µ to 104¢µ), below 80% RH.
- Storage Temperature and Humidity : -10¡É to 60¡É(14¢µ to 140¢µ), below 70% RH.
- Accessories : Test leads Auxiliary¡æ1 Set, Auxiliary earth spikes¡æ2
Pcs,
Neck strap¡æ1 Pcs, Batteries 1.5V AA¡æ 8 Pcs,
Manual |
|
°èÃø±âÀüü¸Þ´º welcome to sjscale@naver.com
Àú¿ï ¹× °èÃø±â±âÀÇ ¸ðµç
°Í(½ÅÁ¤Á¤¹Ð±â°è)
(Tel:055-237-5300~2,FaX:055-237-5007) |